A maximum of 16 isolator units can be connected to each loop, (to meet the requirements of EN54 Pt2) which together with isolators at the beginning and end (internal to the panel), enable a maximum of 17 monitored sections. In the event of a short circuit, isolators disconnect only the section of cable between the two isolators, located electrically closest to the fault. Devices outside the disconnected section continue to operate normally.